NPDES ID: NY0160971
S — SNC: Compliance schedule violation
The facility missed a deadline in its compliance schedule by more than 90 days.
This quarter: 1 effluent violation, 4 permit schedule violations.
Violations
April 30, 2026
Flow, in conduit or thru treatment plant
17% over limit
Discharged 0.007 MGD against a permitted limit of 0.006 MGD (MO AVG)
DMR, Limited - Numeric Violation
March 31, 2026
Nitrogen, ammonia total [as N]
18% over limit
Discharged 13.4 mg/L against a permitted limit of 11.4 mg/L (DAILY MX)
DMR, Limited - Numeric Violation
Flow, in conduit or thru treatment plant
33% over limit
Discharged 0.008 MGD against a permitted limit of 0.006 MGD (MO AVG)
DMR, Limited - Numeric Violation
February 28, 2026
Flow, in conduit or thru treatment plant
4% over limit
Discharged 0.026 MGD against a permitted limit of 0.025 MGD (MO AVG)
DMR, Limited - Numeric Violation
January 31, 2026
Flow, in conduit or thru treatment plant
32% over limit
Discharged 0.033 MGD against a permitted limit of 0.025 MGD (MO AVG)
DMR, Limited - Numeric Violation
December 31, 2025
Flow, in conduit or thru treatment plant
12% over limit
Discharged 0.028 MGD against a permitted limit of 0.025 MGD (MO AVG)
DMR, Limited - Numeric Violation
September 30, 2025
Solids, total suspended
13% over limit
Discharged 17 mg/L against a permitted limit of 15 mg/L (DAILY MX)
DMR, Limited - Numeric Violation
Nitrogen, ammonia total [as N]
446% over limit
Discharged 40.4 mg/L against a permitted limit of 7.4 mg/L (DAILY MX)
DMR, Limited - Numeric Violation
First flagged
April 14, 2026 (3 months ago)
Last confirmed
July 13, 2026 (24 days ago)