IMMACULATA UNIVERSITY STP

NPDES ID: PA0056065

E — SNC: Effluent violation (monthly average limit)

The facility discharged more of a pollutant than its permit allows, based on a monthly average.

This quarter: 11 effluent violations.

Violations

May 31, 2026

Coliform, fecal general

1190% over limit

Discharged 12900 MPN/100mL against a permitted limit of 1000 MPN/100mL (INST MAX)

DMR, Limited - Numeric Violation

BOD, carbonaceous [5 day, 20 C]

30% over limit

Discharged 13 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

Coliform, fecal general

950% over limit

Discharged 2100 MPN/100mL against a permitted limit of 200 MPN/100mL (GEO MEAN)

DMR, Limited - Numeric Violation

Solids, total suspended

324% over limit

Discharged 15.39059987 kg/d against a permitted limit of 3.63199997 kg/d (MO AVG)

DMR, Limited - Numeric Violation

Oxygen, dissolved [DO]

6% over limit

Discharged 6.58 mg/L against a permitted limit of 7 mg/L (INST MIN)

DMR, Limited - Numeric Violation

Solids, total suspended

950% over limit

Discharged 105 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

April 30, 2026

BOD, carbonaceous [5 day, 20 C]

260% over limit

Discharged 36 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

Coliform, fecal general

Limit violation

Discharged 1176 MPN/100mL against a permitted limit of 200 MPN/100mL (GEO MEAN)

DMR, Limited - Numeric Violation

Coliform, fecal general

Limit violation

Discharged 20000 MPN/100mL against a permitted limit of 1000 MPN/100mL (INST MAX)

DMR, Limited - Numeric Violation

Oxygen, dissolved [DO]

3% over limit

Discharged 6.8 mg/L against a permitted limit of 7 mg/L (INST MIN)

DMR, Limited - Numeric Violation

Solids, total suspended

1030% over limit

Discharged 113 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

March 31, 2026

Coliform, fecal general

293% over limit

Discharged 786 MPN/100mL against a permitted limit of 200 MPN/100mL (GEO MEAN)

DMR, Limited - Numeric Violation

Solids, total suspended

680% over limit

Discharged 78 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

Oxygen, dissolved [DO]

28% over limit

Discharged 5.05 mg/L against a permitted limit of 7 mg/L (INST MIN)

DMR, Limited - Numeric Violation

BOD, carbonaceous [5 day, 20 C]

240% over limit

Discharged 34 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

Coliform, fecal general

230% over limit

Discharged 3300 MPN/100mL against a permitted limit of 1000 MPN/100mL (INST MAX)

DMR, Limited - Numeric Violation

February 28, 2026

Solids, total suspended

14% over limit

Discharged 4.13139997 kg/d against a permitted limit of 3.63199997 kg/d (MO AVG)

DMR, Limited - Numeric Violation

BOD, carbonaceous [5 day, 20 C]

570% over limit

Discharged 67 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

Nitrogen, ammonia total [as N]

46% over limit

Discharged 5.4 mg/L against a permitted limit of 3.7 mg/L (MO AVG)

DMR, Limited - Numeric Violation

Oxygen, dissolved [DO]

10% over limit

Discharged 6.33 mg/L against a permitted limit of 7 mg/L (INST MIN)

DMR, Limited - Numeric Violation

Solids, total suspended

1780% over limit

Discharged 188 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

January 31, 2026

Ultraviolet light intensity

0% over limit

Discharged 0 uW/cm2 against a permitted limit of 0 uW/cm2 (INST MIN)

DMR, Monitor Only - Overdue

December 31, 2025

Coliform, fecal general

1700% over limit

Discharged 18000 MPN/100mL against a permitted limit of 1000 MPN/100mL (INST MAX)

DMR, Limited - Numeric Violation

Solids, total suspended

55% over limit

Discharged 5.62959995 kg/d against a permitted limit of 3.63199997 kg/d (MO AVG)

DMR, Limited - Numeric Violation

Solids, total suspended

420% over limit

Discharged 52 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

BOD, carbonaceous [5 day, 20 C]

50% over limit

Discharged 15 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

August 31, 2025

Solids, total suspended

120% over limit

Discharged 22 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

June 30, 2025

Solids, total suspended

20% over limit

Discharged 12 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

May 31, 2025

Coliform, fecal general

480% over limit

Discharged 5800 MPN/100mL against a permitted limit of 1000 MPN/100mL (INST MAX)

DMR, Limited - Numeric Violation

Solids, total suspended

120% over limit

Discharged 22 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

September 30, 2024

Coliform, fecal general

1330% over limit

Discharged 14300 MPN/100mL against a permitted limit of 1000 MPN/100mL (INST MAX)

DMR, Limited - Numeric Violation

Nitrogen, ammonia total [as N]

7% over limit

Discharged 1.6 mg/L against a permitted limit of 1.5 mg/L (MO AVG)

DMR, Limited - Numeric Violation

First flagged

April 14, 2026 (3 months ago)

Last confirmed

July 13, 2026 (23 days ago)