OLATHE HAROLD (MAIN PLANT) (WWTP)

NPDES ID: KS0045802

E — SNC: Effluent violation (monthly average limit)

The facility discharged more of a pollutant than its permit allows, based on a monthly average.

Violations

February 28, 2026

Nitrogen, ammonia total [as N]

75% over limit

Discharged 3.67 mg/L against a permitted limit of 2.1 mg/L (MO AVG)

DMR, Limited - Numeric Violation

January 31, 2026

Nitrogen, ammonia total [as N]

55% over limit

Discharged 13.8 mg/L against a permitted limit of 8.9 mg/L (DAILY MX)

DMR, Limited - Numeric Violation

Nitrogen, ammonia total [as N]

161% over limit

Discharged 5.47444 mg/L against a permitted limit of 2.1 mg/L (MO AVG)

DMR, Limited - Numeric Violation

June 30, 2025

BOD, 5-day, 20 deg. C

17% over limit

Discharged 23.3125 mg/L against a permitted limit of 20 mg/L (MO AVG)

DMR, Limited - Numeric Violation

BOD, 5-day, 20 deg. C

16% over limit

Discharged 34.9 mg/L against a permitted limit of 30 mg/L (MX WK AV)

DMR, Limited - Numeric Violation

First flagged

April 14, 2026 (3 months ago)

Last confirmed

July 13, 2026 (24 days ago)