PICKENS CO PSC CENTRAL-NORTH

NPDES ID: SC0024996

X — SNC: Effluent violation (non-monthly average limit)

The facility discharged more of a pollutant than its permit allows, measured over a period other than a monthly average.

This quarter: 3 effluent violations, 8 single-event violations.

Violations

April 30, 2026

Nitrogen, ammonia total [as N]

16% over limit

Discharged 3.49 mg/L against a permitted limit of 3 mg/L (WKLY AVG)

DMR, Limited - Numeric Violation

BOD, 5-day, 20 deg. C

15% over limit

Discharged 17.3 mg/L against a permitted limit of 15 mg/L (WKLY AVG)

DMR, Limited - Numeric Violation

Nitrogen, ammonia total [as N]

60% over limit

Discharged 3.191 mg/L against a permitted limit of 2 mg/L (MO AVG)

DMR, Limited - Numeric Violation

February 28, 2026

BOD, 5-day, 20 deg. C

35% over limit

Discharged 13.5 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

BOD, 5-day, 20 deg. C

90% over limit

Discharged 28.5 mg/L against a permitted limit of 15 mg/L (WKLY AVG)

DMR, Limited - Numeric Violation

January 31, 2026

BOD, 5-day, 20 deg. C

44% over limit

Discharged 14.4 mg/L against a permitted limit of 10 mg/L (MO AVG)

DMR, Limited - Numeric Violation

First flagged

April 14, 2026 (5 months ago)

Last confirmed

September 15, 2026 (5 days ago)