NPDES ID: OH0125750
E — SNC: Effluent violation (monthly average limit)
The facility discharged more of a pollutant than its permit allows, based on a monthly average.
This quarter: 15 effluent violations.
Violations
June 30, 2026
Nitrogen, ammonia total [as N]
146% over limit
Discharged 0.14 kg/d against a permitted limit of 0.0568 kg/d (MO AVG)
DMR, Limited - Numeric Violation
BOD, carbonaceous [5 day, 20 C]
252% over limit
Discharged 2 kg/d against a permitted limit of 0.568 kg/d (MO AVG)
DMR, Limited - Numeric Violation
BOD, carbonaceous [5 day, 20 C]
1000% over limit
Discharged 110 mg/L against a permitted limit of 10 mg/L (MO AVG)
DMR, Limited - Numeric Violation
E. coli, MTEC-MF
1821% over limit
Discharged 2420 MPN/100mL against a permitted limit of 126 MPN/100mL (MO GEOMN)
DMR, Limited - Numeric Violation
Nitrogen, ammonia total [as N]
840% over limit
Discharged 9.4 mg/L against a permitted limit of 1 mg/L (MO AVG)
DMR, Limited - Numeric Violation
Nitrogen, ammonia total [as N]
527% over limit
Discharged 9.4 mg/L against a permitted limit of 1.5 mg/L (WKLY MAX)
DMR, Limited - Numeric Violation
BOD, carbonaceous [5 day, 20 C]
135% over limit
Discharged 2 kg/d against a permitted limit of 0.852 kg/d (WKLY MAX)
DMR, Limited - Numeric Violation
E. coli, MTEC-MF
752% over limit
Discharged 2420 MPN/100mL against a permitted limit of 284 MPN/100mL (WK GEOMN)
DMR, Limited - Numeric Violation
Oxygen, dissolved [DO]
78% over limit
Discharged 1.1 mg/L against a permitted limit of 5 mg/L (DAILY MN)
DMR, Limited - Numeric Violation
BOD, carbonaceous [5 day, 20 C]
633% over limit
Discharged 110 mg/L against a permitted limit of 15 mg/L (WKLY MAX)
DMR, Limited - Numeric Violation
Solids, total suspended
11% over limit
Discharged 20 mg/L against a permitted limit of 18 mg/L (WKLY MAX)
DMR, Limited - Numeric Violation
Solids, total suspended
67% over limit
Discharged 20 mg/L against a permitted limit of 12 mg/L (MO AVG)
DMR, Limited - Numeric Violation
Nitrogen, ammonia total [as N]
64% over limit
Discharged 0.14 kg/d against a permitted limit of 0.0852 kg/d (WKLY MAX)
DMR, Limited - Numeric Violation
May 31, 2026
E. coli, MTEC-MF
358% over limit
Discharged 1300 MPN/100mL against a permitted limit of 284 MPN/100mL (WK GEOMN)
DMR, Limited - Numeric Violation
E. coli, MTEC-MF
932% over limit
Discharged 1300 MPN/100mL against a permitted limit of 126 MPN/100mL (MO GEOMN)
DMR, Limited - Numeric Violation
February 28, 2026
Solids, total suspended
150% over limit
Discharged 30 mg/L against a permitted limit of 12 mg/L (MO AVG)
DMR, Limited - Numeric Violation
Solids, total suspended
16% over limit
Discharged 0.79 kg/d against a permitted limit of 0.682 kg/d (MO AVG)
DMR, Limited - Numeric Violation
Solids, total suspended
67% over limit
Discharged 30 mg/L against a permitted limit of 18 mg/L (WKLY MAX)
DMR, Limited - Numeric Violation
August 31, 2024
E. coli, MTEC-MF
1821% over limit
Discharged 2420 MPN/100mL against a permitted limit of 126 MPN/100mL (MO GEOMN)
DMR, Limited - Numeric Violation
E. coli, MTEC-MF
752% over limit
Discharged 2420 MPN/100mL against a permitted limit of 284 MPN/100mL (WK GEOMN)
DMR, Limited - Numeric Violation
First flagged
April 14, 2026 (4 months ago)
Last confirmed